Experience with Newport Omega UWTC temp transmitter?
6 posts
• Page 1 of 1
Experience with Newport Omega UWTC temp transmitter?
Hi does anyone have any expierences with Newport Omega UWTC REC3/N and UWTC-2 wifi sensor?
My attached scheme works that i can open and close the port.
But sending commands goes wrong and flowstone locks up. Like readout or password.
Via the webbrowser all works well and i can enter the server directly.
The manual of the device does not give me very much more details.
Any idea if the codes send should be binary or hex or just ascii ?
thanks for any help.
regards,
Jerry
My attached scheme works that i can open and close the port.
But sending commands goes wrong and flowstone locks up. Like readout or password.
Via the webbrowser all works well and i can enter the server directly.
The manual of the device does not give me very much more details.
Any idea if the codes send should be binary or hex or just ascii ?
thanks for any help.
regards,
Jerry
- Attachments
-
- UWTC-client.fsm
- (15.78 KiB) Downloaded 3636 times
- jjanson
- Posts: 10
- Joined: Wed Apr 11, 2012 12:05 pm
Re: Experience with Newport Omega UWTC temp transmitter?
Looks like it is ASCI to me, I found a manual here:
http://www.newportus.com/Pdf/M4620n.pdf
I think as you say you need a more complete data structure with unit ID and password etc.
http://www.newportus.com/Pdf/M4620n.pdf
I think as you say you need a more complete data structure with unit ID and password etc.
- DSP
- Posts: 150
- Joined: Fri May 14, 2010 10:55 pm
Re: Experience with Newport Omega UWTC temp transmitter?
It has been a while but finally it succeeded.
It is in the manual, but when reading it you might not notice.
For people who have such a device and like to experiment with it.
The commands to send to read out the sensor need a * in front of it:
*SRTC to read out degrees in celcius (*SRTF for fahrenheit)
*SRHb for pressure in mbar
*SRH2 for humidity in %
etcetera.
Then it won't give a time out. so simply use the network module, add the port 2000 and the ip nr you've programmed in the sensor/server and send the text command.
see picture
regards.
It is in the manual, but when reading it you might not notice.
For people who have such a device and like to experiment with it.
The commands to send to read out the sensor need a * in front of it:
*SRTC to read out degrees in celcius (*SRTF for fahrenheit)
*SRHb for pressure in mbar
*SRH2 for humidity in %
etcetera.
Then it won't give a time out. so simply use the network module, add the port 2000 and the ip nr you've programmed in the sensor/server and send the text command.
see picture
regards.
- Attachments
-
- read out omega newport sensor
- Capture.JPG (81.34 KiB) Viewed 59299 times
- jjanson
- Posts: 10
- Joined: Wed Apr 11, 2012 12:05 pm
Re: Experience with Newport Omega UWTC temp transmitter?
Hi, now after a while working with and bug finding i noticed a few things.
We have 2 of these envrionment readers, same type but different firmware 1.5 and 1.9.
The fault is that sometimes there is no network connection.
But when accessing via Internet explorer i can acces them both.
After a reset of the devices flowstone can reach them again.
So it seems not a firmware issue as they differ, unless the same fault is in both firmwares.
But with NO reset i CAN acces both via internet explorer.
So now it is a bit confusing were to find the fault, is it flowstone or is the devices.
My guess is that it is flowstone because i have the fault with both devices.
It is very simple connected just an ip adres and a port number, then there a commands send to the reader.
Anyone who had same issues with network setups?
We have 2 of these envrionment readers, same type but different firmware 1.5 and 1.9.
The fault is that sometimes there is no network connection.
But when accessing via Internet explorer i can acces them both.
After a reset of the devices flowstone can reach them again.
So it seems not a firmware issue as they differ, unless the same fault is in both firmwares.
But with NO reset i CAN acces both via internet explorer.
So now it is a bit confusing were to find the fault, is it flowstone or is the devices.
My guess is that it is flowstone because i have the fault with both devices.
It is very simple connected just an ip adres and a port number, then there a commands send to the reader.
Anyone who had same issues with network setups?
- jjanson
- Posts: 10
- Joined: Wed Apr 11, 2012 12:05 pm
Re: Experience with Newport Omega UWTC temp transmitter?
The solution to network dropout was to change the port to 1001.
So it was not a fault of Flowstone.
But the sensor dropped the connection after a while.
So it was not a fault of Flowstone.
But the sensor dropped the connection after a while.
- jjanson
- Posts: 10
- Joined: Wed Apr 11, 2012 12:05 pm
Re: Experience with Newport Omega UWTC temp transmitter?
Hello,
with the network client there must be some kind of bug.
Several times when accessing 1 of the environmental meters we have, we do not get access with the flowstone program.
We also have a separate (pc)servers which is logging the environmetal meters values continuesly thru the day which has always access. Also the server itself (which is built in the environmental meters) are always accessible via their own webpage/address.
The meters are setup to have multiple accesses from different users who can all use the same port on the ip address.
Strange thing is when ressting or repowering the Environmental readers, then Flowstone can suddenly access the readers ???
How can this happen? It seems not to be a failure from the readers itself because they are allways accessible via their own webpage and other used server software(c++/Java) but not always via the client network module in Flowstone.
The client is just simple setup with a IP adress and a port 01001. send a read command and then receive data.
Anyone any idea?
with the network client there must be some kind of bug.
Several times when accessing 1 of the environmental meters we have, we do not get access with the flowstone program.
We also have a separate (pc)servers which is logging the environmetal meters values continuesly thru the day which has always access. Also the server itself (which is built in the environmental meters) are always accessible via their own webpage/address.
The meters are setup to have multiple accesses from different users who can all use the same port on the ip address.
Strange thing is when ressting or repowering the Environmental readers, then Flowstone can suddenly access the readers ???
How can this happen? It seems not to be a failure from the readers itself because they are allways accessible via their own webpage and other used server software(c++/Java) but not always via the client network module in Flowstone.
The client is just simple setup with a IP adress and a port 01001. send a read command and then receive data.
Anyone any idea?
- jjanson